MC (Metal-Clad) cable is a factory-assembled wiring system with insulated conductors in metal armor, for residential, commercial, and industrial use.
Recognized under National Electrical Code (NEC) Article 330, metal-clad cable is built for power distribution, lighting, control, and signal circuits where physical protection matters. Its metal armor shields the conductors inside, making it suitable for exposed runs and areas vulnerable to impact.
What Exactly Is an MC Cable?
MC cable is a factory assembly of insulated circuit conductors enclosed in a flexible metal armor. That armor comes in several forms — interlocking aluminum tape (AIA), smooth or corrugated steel, and continuously corrugated copper weld (CLX). Each type trades weight, flexibility, and corrosion resistance differently, but all serve the same purpose: mechanical protection without the need for conduit.
A critical point that catches many installers: the metal armor itself is not a recognized equipment grounding conductor in standard MC cable. A dedicated bare or insulated grounding conductor must run inside the cable alongside the circuit conductors. Some MC variants include a bare aluminum bonding wire in constant contact with the armor for redundant grounding, but a full-size ground wire is always required.
MC cable is manufactured to UL 1569 and meets federal specification A-A59544. Conductors range from #18 AWG to 750 KCMIL, with THHN/THWN-2 insulation rated for 90°C in dry locations and 75°C in wet locations.
When you need a specific conductor size for your project, our roundup of the top-rated 8-2 MC cable options covers tested products and what to look for before buying.
| Specification | Details |
|---|---|
| Voltage Rating | Up to 600V; 120–208V and 277/480V models available |
| Temperature Rating | 90°C dry / 75°C wet (THHN/THWN-2) |
| Conductor Sizes | #18 AWG to 750 KCMIL |
| Armor Types | Aluminum interlocked, steel, corrugated copper |
| Grounding | Dedicated ground wire required (armor is not ground) |
| UL Standard | UL 1569 |
| Flame Test | IEEE 1202 (70,000 BTU/hr vertical tray) |
Where Is MC Cable Permitted?
The NEC allows MC cable for services, feeders, and branch circuits in residential, commercial, industrial, and non-patient areas of health care facilities. It works for power, lighting, control, and signal circuits in dry locations — including runs embedded in plaster finish on brick or masonry.
Standard MC cable is not allowed in wet locations, direct burial, underground conduit, or overhead runs in wet conditions. For damp or wet environments, you need a PVC-jacketed “All Purpose” variant like Southwire’s 60250MC-AP HCF cable, which adds a moisture barrier to the assembly.
How Is MC Cable Installed?
Installation follows straightforward NEC rules, but a few steps are easy to get wrong.
Removing the armor. Pull off the metal sheathing and any plastic wrap underneath.
Connectors and the anti-short bushing. Insert the cable into an approved connector, tighten it firmly to both the box and the cable, and make sure the anti-short bushing is plainly visible for inspection. The bushing prevents the armor’s cut edge from digging into the conductor insulation.
Grounding is where most mistakes happen. Never assume the aluminum armor provides the ground path. The dedicated grounding conductor must be properly terminated at every junction. Southwire’s Armorlite MC cable specifications confirm the grounding requirements and available configurations.
Common mistakes. Each one is avoidable with proper technique.
FAQs
Can MC cable be used in wet locations?
Standard MC cable is rated for dry locations only. For wet locations, direct burial, or underground conduit, you need a PVC-jacketed “All Purpose” MC cable variant that meets NEC moisture-protection requirements.
Does MC cable need conduit?
No. MC cable is a complete wiring method and does not require additional conduit for indoor installations. The metal armor provides equivalent physical protection in most NEC-permitted locations, which is one of its main advantages over THHN wire in conduit.
How is MC cable different from AC cable?
The key difference is grounding. In Type AC cable, the armor serves as the equipment grounding conductor. In MC cable, the armor is not a recognized ground path — a dedicated bare or insulated grounding conductor must run inside the cable alongside the circuit conductors.
References & Sources