MC cable size charts are manufacturer tables matching conductor gauge and count to cable diameter, weight, and ampacity for a product family.
When specifying Type MC (metal-clad) cable for commercial or industrial work, an MC cable size chart is the essential reference linking conductor gauge, count, and ground size to a specific product’s outside diameter, weight, and ampacity. Unlike standard building wire, MC cable is a factory-assembled system with conductors bundled inside a metallic sheath, so overall diameter and ampacity depend on conductor size, insulation type, jacket material, and armor construction. There is no single universal chart; each manufacturer publishes its own table because those variables change final dimensions. The NEC covers Type MC cable under Article 330, with permitted sizes ranging from 18 AWG through 2000 kcmil for copper and 12 AWG through 2000 kcmil for aluminum or copper-clad aluminum.
What Is An MC Cable Size Chart?
An MC cable size chart is a product-specific lookup table listing available conductor sizes, count, ground size, outside diameter, weight, and ampacity for a particular Type MC cable family. The chart belongs to a specific product line and manufacturer — Kingwire, Service Wire, and others each maintain their own specs because MC cable construction varies. Smooth-sheathed and interlocked-armor cables have different diameter profiles, and jacketed versus unjacketed versions change outer dimensions significantly. The chart also shows weight per thousand feet for pulling tension and support spacing. Using the wrong manufacturer’s chart can cause fit problems at junction boxes, incorrect ampacity assumptions, and code violations during inspection.
How MC Cable Sizing Works In Practice
To size MC cable correctly, start with the number of conductors needed, required ampacity, and installation environment — then find the matching entry in the manufacturer’s published table.
Conductor notation on MC cable labels is read sequentially: 6-6-6-6 means three 6 AWG phase conductors plus a 6 AWG ground, while 4-4-4-6 means three 4 AWG phase conductors plus a 6 AWG ground. Kingwire’s MC cable specification sheet lists these configurations with measured outside diameters and dual temperature ampacity ratings.
Service Wire’s feeder MC table uses model names like MC8/4 through MC600/4. An MC8/4 cable contains four 8 AWG conductors and measures roughly 0.89 inches in diameter. At the larger end, MC600/4 holds four 600 kcmil conductors and reaches 2.71 inches. All ampacity values reference NEC Table 310.15(B)(16), with the note that four-conductor ampacity assumes three conductors are hot and one is neutral. For smaller branch circuits using 14 AWG conductors, the best 14-2 MC cable options show what to check in diameter, ground size, and ampacity.
| Conductor Configuration | Outside Diameter | Ampacity (75°C Copper) |
|---|---|---|
| 6-6-6-6 (3×6 AWG + 6 AWG gnd) | 0.78 in | 50/55 A |
| 4-4-4-6 (3×4 AWG + 6 AWG gnd) | 0.88 in | 65/75 A |
| 2-2-2-6 (3×2 AWG + 6 AWG gnd) | 1.00 in | 90/100 A |
| MC8/4 (4×8 AWG) | 0.89 in | Per NEC 310.15(B)(16) |
| MC4/4 (4×4 AWG) | — | Per NEC 310.15(B)(16) |
| MC1/4 (4×1 AWG) | — | Per NEC 310.15(B)(16) |
| MC600/4 (4×600 kcmil) | 2.71 in | Per NEC 310.15(B)(16) |
Ampacity, Securing, And Installation Rules
MC cable ampacity is drawn from NEC Table 310.15(B)(16) and must be derated when conditions reduce heat shedding. Derating applies when more than three current-carrying conductors are present, ambient temperature exceeds 30°C (86°F), or more than two Type MC cables are bundled in thermal insulation. These adjustments are not optional — inspectors will check them.
Securing rules for Type MC cable with four or fewer conductors no larger than 10 AWG require support within 12 inches of every box, cabinet, or fitting and at intervals not exceeding 6 feet. For vertical installations using 250 kcmil and larger ungrounded conductors, the support interval extends to 10 feet. Bending radius depends on sheath type: smooth-sheathed MC cable up to 3/4 inch external diameter requires an inner-edge bend radius of at least 10 times the metallic sheath diameter; interlocked-armor MC cable requires 7 times the external diameter.
Common mistakes include treating all MC cable as interchangeable between manufacturers, confusing overall cable diameter with conductor gauge, and skipping derating calculations for bundled conductors or cables run through insulation. Always confirm the specific product’s published diameter and ampacity against your installation conditions before ordering.
FAQs
What “4-4-4-6” Means On An MC Cable Label
The notation lists conductor sizes separated by hyphens: three 4 AWG conductors (typically hot phases) plus one 6 AWG ground wire. The order usually follows phase conductors first, then the ground or neutral size.
Can I Use One Manufacturer’s Chart For Another Brand?
No. MC cable dimensions vary by manufacturer due to differences in insulation thickness, jacket material, and armor construction. Always use the specific manufacturer’s published spec sheet.
MC Cable Versus AC Cable
Type MC (metal-clad) cable includes a full-size equipment grounding conductor and can be used in a wider range of applications. Type AC (armored cable) uses the armor as the ground path and is limited to certain dry locations per NEC Article 320.
References & Sources
- Kingwire. “MC Cable Specification Sheet.” Published spec data for three-conductor-with-ground MC cable sizes and ampacity.
- Service Wire. “Feeder MC 4-Conductor Cable Specification.” Feeder MC cable sizes, diameters, and ampacity per NEC Table 310.15(B)(16).
- National Electrical Code. “NEC Tables and Articles.” Code reference for Article 330, securing rules, and ampacity derating.